OPCUA-PLC
所属分类:单片机开发
开发工具:Python
文件大小:0KB
下载次数:0
上传日期:2023-12-21 21:22:17
上 传 者:
sh-1993
说明: OPCUA可编程逻辑控制器
(OPCUA PLC)
文件列表:
src/
tests/
.DS_Store
Industrial_product.png
PLC_SY.lld
requirements.txt
## Python3.7 Virtual Environment Dependencies
```javascript
pip install -r requirements.txt
```
### Usage
To Set the `OPC-UA` server:
```
python src/plc_simulator.py
```
Check logs:
```
tail -f plc_simulator.log
```
To run the tester:
```
python -m pytest tests
```
The `PLC_SY.lld` file is the ladder code where Siemens LOGO!Comfort software was used
#### Tester
* GRAFCET logic: `test_aa_grafcet.py`
* Tank high level: `test_alarm_0.py`
* Tank low level: `test_alarm_1.py`
* High temperature (>80): `test_alarm_2.py`
* Low temperature (<10): `test_alarm_3.py`
* Discharging door open: `test_alarm_4.py`
* Emergency activated: `test_alarm_5.py`
## Digital Inputs (DI):
- DI0: START BUTTON
- DI1: RUN BUTTON
- DI2: STOP BUTTON
- DI3: EMERGENCY BUTTON
- DI4: RESET BUTTON
- DI5: LOWER LEVEL FLOATER
- DI6: LOW LEVEL FLOATER
- DI7: HIGH LEVEL FLOATER
- DI8: HIGHER LEVEL FLOATER
- DI9: DISCHARGING GATE SENSOR
## Digital Outputs (DQ):
- DQ0: INPUT VALVE
- DQ1: OUTPUT VALVE
- DQ2: HEATING SYSTEM VALVE
- DQ3: MOTOR-CONTROLLED DISCHARGING GATE
## Analog Inputs (AI):
- AI0: SENSOR TEMPERATURE
## Alarms:
- A0: Tank high level
- A1: Tank low level
- A2: High temperature (>80)
- A3: Low temperature (<10)
- A4: Discharging door open
- A5: Emergency activated
### Main Procedures Logic Table
#### STARTING
| Condition | Action/Procedure | Logic (0, 1) |
|------------------------------------|----------------------------------------------|--------------|
| Start button pressed (DI0 is True) | If DI9 is True, Close motor-controlled discharging door (DQ3 = False) | 0, 1 |
| Start button pressed (DI0 is True) | Open In Valve (DQ0 = True) until DI6 is True; | 1 |
| Tank level reached (DI6 is True) | Close In Valve (DQ0 = False) | 0 |
#### RUNNING
| Condition | Action/Procedure | Logic (0, 1) |
|---------------------------------|-------------------------------------------|--------------|
| DI1 is True | Open In Valve ; RUN button pressed | 1 |
| High level not reached (DI7 is False)| Continue tank filling process | 1 |
| High level reached (DI7 is True) | Close In Valve; Start Heating System | 0, 1 |
#### HEATING
| Condition | Action/Procedure | Logic (0, 1) |
|---------------------------------------------|----------------------------------------------|--------------|
| Tank is full (DI7 is True) | Start heating process | 1 |
| Temperature below setpoint (AI0 < Setpoint) | Continue heating | 1 |
| Temperature at or above setpoint (AI0 >= Setpoint)| Stop Heating System | 0 |
#### DISCHARGING
| Condition | Action/Procedure | Logic (0, 1) |
|------------------------------------|-------------------------------------------|--------------|
| Start discharging process | Open Out Valve (DQ1 = True) | 1 |
| Low level not reached (DI6 is False)| Continue waiting for low level | 1 |
| Low level reached (DI6 is True) | Close Out Valve (DQ1 = False) | 0 |
### Alarms Logic Table
| Alarm | Condition | Action | Logic (0, 1) |
| --- | --- | --- | --- |
| A0 (Tank High) | DI7 is True | Set Active | 1 |
| A1 (Tank Low) | DI5 is True | Set Active | 1 |
| A2 (Temp High) | AI0 > 80 | Set Active | 1 |
| A3 (Temp Low) | AI0 < 10 | Set Active | 1 |
| A4 (Door Open) | DI9 is True | Set Active | 1 |
| A5 (Emergency) | DI3 is True | Set Active | 1 |
### Extra features
Pressure sensors could be added to the INPUT and OUTPUT valves to ensure the amount of water is the same in case of a clogged pipe